Description
Conventional Fire Alarm Control Panel Features
1, Up to 16 zones can be detected, compatible with conventional detectors and manual call points. Each of the 16 zones can be individually configured as maximum 15 conventional detectors. The total number of detectors and manual call points in a zone shall not exceed 32.
2, Three sounder outputs, one alarm output, one fault output and one disable/supervisory output.
3, Able to report short and open circuits of zones, sounder outputs and alarm output.
4, Test and disable functions.
5, Programmable on manual call point connection, sound modes, sounder delay modes and output delay modes.
6, Three access levels settable via the key switch and the internal switch.
7, Providing external ports includes RESET, EVAC, SILENCE.
8, Designed with standby batteries and space provision for two sealed lead-acid batteries.
Technical Specifications
Input Voltage: 100V~230VAC(+10%-15%), 50/60Hz
Input Current: 1.2 A
Fuse: 250VAC, T2A in SPS
Recommended Wiring: 1.5mm2 or above shield cable, complying with local installation codes.
Note: External overcurrent protection device is required and should be installed near the
Operating Voltage:
Minimum Operating Voltage: 21.5V
Maximum Charging Current: 350mA
Maximum Charging Voltage: 27.6V
Battery Type: Sealed lead-acid battery
Maximum Battery Charging Capacity: 2 batteries, 7Ah/12V.
Recommended Battery Manufacturer and Model: Yuasa NP7-12
Maximum internal resistance of the batteries: 1Ω
Standby current of batteries when fully load: 0.1A
Maximum operating current of the batteries: 2.1A
Detection Zone:
The FACP provides maximum 16 zones; each can be individually configured with maximum 15
conventional detectors.
Output voltage: 18VDC~28VDC
Standby current: less than 6mA (connecting with 15 conventional detectors)
Alarm current: about 25mA
End-of-line-resistor: 4.7kΩ
Resistance range for fire alarm: 150Ω~1.5kΩ (normally 510Ω)
Recommended wiring: 1.0mm2 or above shield cable, complying with local installation codes. Recommended cable length: no longer than 1000m
Output Interface:
Fault output
Type: normally open/close contact output
Contact capacity: 1A/24VDC
Disable/supervisory output (defaulted disable output)
Type: normally open/close contact output
Contact capacity: 1A/24VDC
Alarm output
Type: voltage output, normally open/close contact output are available (defaulted voltage output)
Contact capacity: 1A/24VDC
Output voltage: 18VDC~28VDC
Output current: 300mA in alarm
End-of-line-resistor: 4.7kΩ
Sounder 1# output
Type: voltage output, normally open/close contact output (defaulted voltage output)
Contact capacity: 1A/24VDC
Output voltage: 18VDC~28VDC
Output current: 300mA in alarm
End-of-line-resistor: 4.7kΩ
Sounder 2#~3# output
Type: voltage output
Output voltage: 18VDC~28VDC
Output current: 300mA in alarm
End-of-line-resistor: 4.7kΩ
Auxiliary Power Output
Output voltage: 18VDC~28VDC
Output current: 20mA in standby and maximum 500mA in alarm
Recommended wiring: 1.0mm2 or above shield cable, complying with local installation codes. Recommended cable length: no longer than 1000m
Input Interface (For future use)
RESET/EVAC/SILENCE input
Type: normally open contact input
Recommended wiring: 1.0mm2 or above shield cable, complying with local installation codes. Recommended cable length: no longer than 1000m
Installation and Storage
The FACP is applicable for indoor use below the elevation of 2000m. Overvoltage level is Class II and
pollution degree is 2.
Installation Environment
Temperature: -5℃~50℃, Relative humidity≤95%, non-condensing
Storage Environment: Temperature: -25℃~50℃, Relative humidity≤95%, non-condensing