EP-Type-Linear-Heat-Sensing-Cable

Linear Heat Sensing Cable EP Type

Explosion proof type of LHSC is used in two main application environments: harsh EMI environment and explosive hazardous environment.

SKU:

DHI-HY-TSC-40DA-EP

Certification:

CE,UL

Brand:

Description

Linear Heat Sensing Cable EP Type – Overview

Linear Heat Detection (LHD) is a continuous heat detector in the form of a cable. It can detect heat at any points along its entire length. Linear Heat Detector is composed of Linear Heat Sensing Cable (LHSC), adapter unit and termination unit. The digital LHSC is composed of two twisted shield conductors insulated with a heat sensitive material, then wrapped with a protective tape and finished with an outer jacket. The heat sensitive material will soften and fuse at specific fixed temperature which causes the contact of the conductors, the short circuit will trigger an alarm to the Fire Alarm Control Panel (FACP), thus realize the function of fire detection and warning.

Technical Specification

Material of Core Conductor Steel
Diameter of Core Conductor 0.92 mm (0.04″)
Length of Cable 200 m (656 ft), 500 m (1640 ft)
Resistance of Core Conductor
(Two-cores, 25°C)
0.64 ± 0.06 Ω/m
Min Bend Radius 15 cm (5.9″)
UL Approvals / Max. Listed Spacing 15.2 m (50 ft)
Alarm Temperature 68°C (154°F) 88°C (190°F) 105°C (221°F) 138°C (280°F)
Accuracy ±3°C (±5.4°F) ±5°C (±9.0°F) ±5°C (±9.0°F) ±5°C (±9.0°F)
Responding Time ≤ 10 s ≤ 10 s ≤ 15 s ≤ 20 s
Color of Outer Jacket Silver
Operating Temperature −40°C to +45°C (−40°F to +113°F) −40°C to +60°C (−40°F to +140°F) −40°C to +75°C (−40°F to +167°F) −40°C to +93°C (−40°F to +199°F)
Storage Temperature −20°C to 50°C (−4°F to +122°F)
Operating Humidity ≤ 95% RH (non-condensing)

 

Related Products