Addressable 4 wire Natural Gas&LPG Detector with Relay DHI-HY-AA340R_Front Addressable 4 wire Natural Gas&LPG Detector with Relay DHI-HY-AA340R_Left_45° Addressable 4 wire Natural Gas&LPG Detector with Relay CE

Addressable 4 wire Natural Gas LPG Detector with Relay

Addressable Gas Detector DHI-HY-AA340R is a safety devicemonitoring ambient methane (CH4) or propane (C3Ha) concentration(mutually exclusive configuration). Triggers alarms upon reachingpreset thresholds and initiates fire suppression systems via integratedcontrol loops to mitigate explosion risks, ensuring personnel safety andproperty protection.Gas detectors are safety devices for continuous monitoring ofambient Natural Gas or LPG concentrations. Upon detecting leaksexceeding preset thresholds, they trigger alarms and linkage the firedevice through fire alarm system-to prevent explosions and protectpersonnel/property.

SKU:

DHI-HY-AA340R

Certification:

CE

Brand:

Description

Feature – Addressable 4 wire Natural Gas LPG Detector with Relay

High-Sensitivity Detection: Incorporates pellistor sensors toprecisely identify gas leaks, triggering alarms at 8% LEL (±3% LEL accuracy threshold).

Selectable Relay Output Types: Jumper-selectable dry contactsignal type (NO or NC)

Selectable Gas Types: Jumper-selectable gas type Natural (Gasor LPG)

Short Warm-up Time: This gas detector achieves warm-up timesbelow industry averages, enabling faster operational readinesscompared to mainstream alternatives.

Two-wire and Polarity-free Design: Two-wire polarity-free designsignificantly simplifies installation and maintenance operations.

Technical Information

Parameter Introduction
Working Principle Natural Gas (methane) or LPG (propane)
Operating Voltage DC 24V
Operating Current
  • Static current: ≤ 30mA
  • Alarm current: > 35mA
Alarm Mode Indicator light alarm
Operating Temperature −10°C to +55°C (+14°F to +131°F)
Operating Humidity ≤ 95% RH (no condensation)
Dimensions Φ100 mm × 46.3 mm (Φ3.94″ × 1.82″)
Weight 105 g (0.231 lb)
Color White
Installation
  • Detection of methane: Ceiling mount, distance from roof ≤30 cm
  • Detection of propane: Wall mount, distance from the ground ≤30 cm
Detection Capability
  • Detection range of 0% to 100% LEL
  • Alarm threshold: 8% ± 3% LEL
Certification CE

 